|
BACK |
|
PARTIAL DISCHARGE (PD) TESTING OF M.V / H.V INSTRUMENT TRANSFORMER |
|
1.0 PD testing of Instrument Transformers :
Partial Discharges (PD) in the high voltage insulation are local breakdowns
of the insulation
Current transformers and Potential transformer are very important equipments
of any power 1.1 Short circuit fault in the system, 1.2 Damage to other surrounding equipment / switchgear and1.3 Cause Non-availability of the system. 2.0 Reasons for PD in Instrument Transformers :
The instrument transformers when manufactured in factory due to its
manufacturing process 3.0 Test Description and Set up :
For this test rated phase to neutral voltage is applied across the object. A
coupling capacitor |
|
|
|
4.0 Limiting values and Testing schedule :
As per
Indian Standard (IS) 11322 - the limiting value of PD in Cast resin
instrument PD Testing of instrument transformers should be carried out 4.1 Just before commissioning to have the base foot print values at site. 4.2 Once in every 2 years to trend the ageing or increase in the pC value and 4.3 Depending upon the pC value measured over a period of six or twelve months.
5.0 Test Equipment and Experience :
Power – Linker group is already working for condition monitoring and
diagnostic analysis of You may write to us for any of your requirement of PD testing of instrument
transformer. For
|