CONDITION MONITORING & DIAGNOSTIC TESTING OF
                      

Back


      GENERATORS (> 5 MW)

 

      RECOMMENDED TEST AS PER IEC

 

 

§         Tests on Stator

·    Insulation Resistance and Polarization Index Measurement at recommended test voltage.

·    Capacitance and Tan delta Measurement at 10 kV or Uo Voltage whichever is less.

·    Partial Discharge Measurement at 10 kV or Uo Voltage whichever is less.

·    DC / AC Leakage current Measurement (Hi-Pot test).

·    DC Winding Resistance Measurement at 1A /10A DC constant source.

·    Electro Magnetic Core Imperfection Detection (ELCID) test.

 

§         Tests on Rotor

·    Insulation Resistance and Polarization Index Measurement at recommended test voltage.

·    DC Winding Resistance Measurement at 1A /10A DC constant source.

·    AC Winding Impedance Measurement.

·    RSO Test (Recurrent Surge Oscillograph test)

 

§         Tests on Exciter Stator and Rotor

·    Insulation Resistance and Polarization Index Measurement at recommended test voltage.

·    DC Winding Resistance Measurement at 1A /10A DC constant source.

·    AC Winding Impedance Measurement.     

·    Checking of diodes and fuses.

 

§         Tests on PMG

·    Insulation Resistance and Polarization Index Measurement at recommended test voltage.

·    DC Winding Resistance Measurement at 1A /10A DC constant source.

·    AC Winding Impedance Measurement.     

 

Click here to download this page 

                                                                                              TOP                                                        Updated on 27.08.2010