Home
                     

Home

Company Profile services Infrastructure Experience Enquiry Vacant Positions Online Resume Submission


LIST OF TESTING INSTRUMENTS FOR CONDITION MONITORING AND DIAGNOSTIC TESTING
                                                                                                                            

BACK



         
1.0   Capacitance and Tan d test set :


          The operation of the condition monitoring testing instrument is fully controlled by PC (Laptop) and supervised by 
          sophisticated software. This software controls the complete test procedure, collects the test data, analyses the 
          data, display the same in tabular and graphical format. The test data for respective equipments are stored for
          establishing the trending periodically, which is very important for any condition monitoring testing.

  

           1.1    Laptop with latest configuration with all licensed software

           1.2
   User friendly Visual C++ windows Software for operation, data collection, data retrieving
                  for C & Tan d test.


          
1.3    Measuring range of bridge for Tan d: 0 to 100 % Resolution 1x 10 4  accuracy + 1% of
                  the reading up to 20% range.


          
1.4   Measuring range of bridge for capacitance: 10pF to 1mF and Resolution  0.1pF on lowest
                 range and accuracy + 0.25 % of the reading.


           1.5   Calibration unit for validating accuracy even at site.

           1.6   Induction cancellation for 400kV switchyard operation.

           1.7    0-12kVAC supply with 200 m A continuous and 400 m A intermittent (15 min.)

           1.
8   Resonating Inductor with current rating up to 3Amps. (Satisfy the rating to test up to
                  250MW-machine with13.5KV Line Voltage)
        

 

          2.0  Tan d, dielectric constant and Resistivity test with Oil Cell and Oil cell Heater:
           
          2.1
   Output with 0-2 KVAC,0-1KVDC output

          2.2    Oil test cell as per BIS standards

          2.3    Heater for Temp, up to 150 °C
 

        3.0   Partial Discharge measurement equipment with Oscilloscope.
        4.0   Motorized megger with 500,1000,2500 & 5000V DC different supply with external
                Discharge facility for measurement of Dielectric absorption Test, IR value and PI value.

        5.0  Digital Dual Channel Storage oscilloscope Make : Tektronix, USA  with PC communication
                software.

        6.0  Rotor Reflectometer, Type : TDR, 
               
Make : Convex Design Ltd., Bristol, England.
               This is a world renowned, highly accurate Rotor Reflectometer for Recurrent Surge Oscillograph test.
               There are several modes in which the Reflectometer can be used.
               These are,
               a) Testing of stationary rotor within generator.
               b) Testing of rotor at speed within generator (unexcited)
               c) Testing of rotor when removed from generator

               Testing set can be used for,
               a) Fault between winding and rotor body (earth fault).
               b) Inter turn fault.
               c) High resistance joint in rotor.
               d) Inter winding fault.
 

Click here to download this page
                                                                                                                                                                     

TOP


                                                                                                                                                                     Update : 13.01.06